Series Intelligent Duct Smoke Detectors
Intelligent Model Available ED-DPR: Duct Housing ED-DP(I): Duct Sensor Head *I denotes isolator version
Product Overview Air velocity rating from 500 to 4000 feet per minute (2.54 to 20.32 m/sec.) Operates from the control panel communication line Continuous sensitivity monitoring from the panel Intelligent photo isolator or non-isolator heads with twist-in/twist-out removal Easy to clean UL recognized field-replaceable power boards Transparent cover for convenient visual inspection UL 268A listed 3-year warranty Has outputs for remote LED display, remote test Requires com line power only Powered outputs for remote LED, and remote test and sounder Remote test station and remote annunciator accessories The System Sensor EclipseTM Series photoelectric air duct smoke detectors are capable of sensing smoke in air velocities from 500 to 4,000 feet per minute (2.54 to 20.32 m/sec). The Eclipse Series ED-DPR duct housing can accommodate either the ED-DP or ED-DPI Intelligent Photoelectric Sensor. The twist-in, twist-out heads allow for quick and easy cleaning or application changes without removing the duct housing. The Eclipse Series Detector samples air currents passing through a duct and gives dependable performance for shutdown of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke and fire gases through the protected area. These intelligent sensors communicate and are continuously monitored through the communication line. Detector sensitivity changes caused by dirt, temperature, or humidity are reported to the panel, allowing compensation algorithms to maintain the sensor's set sensitivity. An advance indication at the panel specifies the sensor address, allowing for selected maintenance to be performed as needed. Remote alarm annunciation can be accomplished by using the RA400Z Remote Annunciator or the RTS451 or RTS451KEY Remote Test Station. Both these devices allow testing of the detector from a remote location. The Eclipse Series is designed for simplified installation and easy maintenance. WARNING: Duct smoke detectors have specific limitations. DUCT SMOKE DETECTORS ARE: NOT a substitute for an open area smoke detector, NOT a substitute for early warning detection, and NOT a replacement for a building's regular fire detection system. Refer to NFPA 72 and 90A for additional duct smoke detector application information.
APPROVED
S911
Architect/Engineer Specifications The duct smoke detector shall be a System Sensor Model ED-DPR Intelligent Duct Smoke Detector to be used with compatible control panels. The duct smoke detector shall be UL listed per UL 268A, Standard for Smoke Detectors for Duct Applications, specifically for use in air handling systems. The detector shall operate in air velocities from 500 to 4000 feet per minute. The detector housing shall be equipped with an integral mounting base capable of accommodating either the EDDP or ED-DPI photoelectric detector head. It shall be capable of remote testing from the RTS451 or RTS451KEY Remote Test Station. The duct smoke detector housing shall incorporate an airtight smoke chamber in compliance with UL 268A. The housing shall be capable of mounting to either rectangular or round ducts without adapter brackets. An integral filter system shall be included to reduce dust and residue effects, thereby reducing maintenance and servicing. Sampling tubes shall be easily installed after the housing is mounted to the duct by passing through the duct housing. Terminal connections shall be of the strip and clamp method suitable for 14-18 AWG wiring.
Wiring diagram for ED-DPR Duct Smoke Detector using a UL listed control panel
(+) COM LINE
LISTED COMPATIBLE CONTROL PANEL
SLC +
TO REST OF SYSTEM
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1
2
3
1
2
3
(-) COM LINE TO REST OF SYSTEM 1 2
3
SLC OPTIONAL RETURN LOOP
Note: For terminals 9 through 14, normally closed and normally opened relay positions are defined with product in reset condition, not in alarm. Wiring diagram for ED-DPR Duct Smoke Detector with optional RA400Z
6 (+)
4
(+)
(-)
RED
(-)
RA400Z REMOTE ANNUNCIATOR
DUCT DETECTOR
Break Tab on RA400Z for use with ED-DPR.
Wiring diagram for ED-DPR Duct Smoke Detector with RTS451/RTS451KEY
RTS451/ 451KEY GROUND
TEST (+)
5
1 2 ALARM (LED)
4
8
7 4 TEST (+)
TEST (-)
5
TEST (-)
DUCT DETECTOR
RTS451/RTS451KEY REMOTE TEST STATION
ED-DPR Specifications Current Requirements (using no accessories) Power supply voltage Max. standby current Max. alarm current Alarm response time Power up time Self test initiation time 14-30VDC 360 A max. 7 mA max. @ 24VDC (LEDs on) 30 sec. 2 sec. 1 sec.
Relay Contact Ratings (Each set of Form C Contacts) CURRENT RATINGS 3A 2A .9A .9A .5A 1A .3A .7A 1.5A MAXIMUM VOLTAGE 30VDC 30VDC 110VDC 125VAC 30VDC 30VDC 125VAC 75VAC 25VAC LOAD DESCRIPTION Resistive Resistive Resistive Resistive Inductive (L/R=5ms) Inductive (L/R=2ms) Inductive (PF=.35) Inductive (PF=.35) Inductive (PF=.35) APPLICATION Non Coded Coded Non Coded Non Coded Coded Coded Non Coded Non Coded Non Coded
Accessory Current Loads at 24VDC Device RA400Z RTS451/RTS451KEY Standby 0 mA 0 mA Alarm 4.6 mA Max. 4.6 mA Max.
Specifications Operating Temperature Range 32 to 120F (0 to 49C) Operating Humidity Range 10% to 93% relative humidity (non-condensing) Duct Air velocity 500 - 4000 ft./min. (2.54 - 20.32 m/s) Shipping Weight ED-DPR: 4lbs. (1.8 kg) Length 14.5 (36.7 cm) Width 5 (12.7 cm) Depth 4 (10.2 cm)
Ordering Information Par t No. ED-DPR ED-DP ED-DPI ST-1.5 ST-3 ST-5 ST-10 A2121 Description Eclipse Series intelligent duct smoke detector housing Photoelectric duct sensor head Photoelectric isolator duct sensor head Metal sampling tube duct widths 1-2 Metal sampling tube duct widths 2-4 Metal sampling tube duct widths 4-8 Metal sampling tube duct widths 8-12 Replacement Eclipse Power Board Accessories RTS451 RTS451KEY RA400Z F36-05-00 P48-21-00 T80-71-00 Description Remote test station (see below) Remote test station w/key (see below) Remote LED (see below) Replacement filters End cap for metal sampling tube Replacement plastic sampling tube
ALARM
ALARM
RESET
ON
TEST
RESET
RTS451 Remote Test Station (UL S2522)
RTS451KEY Remote Test Station with key (UL S2522)
RA400Z Remote Annunciator (UL S2522)
System Sensor Sales and Service
System Sensor Headquarters 3825 Ohio Avenue St. Charles, IL 60174 Ph: 800/SENSOR2 Fx: 630/377-6495 Documents-on-Demand 800/736-7672 x3 www.systemsensor.com System Sensor Canada Ph: 905.812.0767 Fx: 905.812.0771 System Sensor Europe Ph: 44.1403.891920 Fx: 44.1403.891921 System Sensor in China Ph: 86.29.524.6253 Fx: 86.29.524.6259 System Sensor in Singapore Ph: 65.6273.2230 Fx: 65.6273.2610 System Sensor - Far East Ph: 85.22.191.9003 Fx: 85.22.736.6580 System Sensor - Australia Ph: 613.54.281.142 Fx: 613.54.281.172 System Sensor - India Ph: 91.124.237.1770 x.2700 Fx: 91.124.237.3118 System Sensor - Russia Ph: 70.95.937.7982 Fx: 70.95.937.7983
(c) 2004 System Sensor. The company reserves the right to change product specifications without notice.
A05-0373-000*4/04*#1261


▲Up To Search▲   

 
Price & Availability of A2121

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X